/fs/cache/7c/63/48/0c/12e1490b775d220ea0f725b8.jpg

ВД2M Type Rectifiers for Power Supply of Metro Contact Networks

  • Types of produced rectifiers are shown in the table below:

VD2M-1600-825 UHL4

For the metro with 10-12 cars in the train

VD2M-1600-825-1 UHL4

For the metro with 4-5 cars in the train

  • Climatic version of the rectifier - UHL for macroclimatic areas with a temperate and cold climate, placement category 4 according to GOST 15150-69 and GOST 15543.1-89.
  • The rectifier is designed to work when installed at a height of no more than 1000 m above sea level, the working value of the ambient air temperature is from + 1 to + 35 C and relative humidity of 60% at 20 C. Limit operating values of ambient air temperature from + 1 to + 40 C and relative humidity of air 80% at 25 C.
  • Rectifier VD2M has a microprocessor control, protection and alarm system (based on Siemens), which allows you to adapt this device to the automated control system of the traction substation complex.

Parameters

General Specification:

Parameters

Values

VD2M-1600-825

VD2M-1600-825-1

Nominal rectified current, A

1600

Nominal rectified voltage, V

825

 Linear input voltage, V

625 

 Rectification scheme

Three-phase bride

 Cooling

Natural air 

 Diode type

 ДЛ-173-4000-20

ДЛ153-2500-20

 Number of diodes

12 

 Input voltage tolerance, %

+10; -5 

 Frequency of input voltage, Hz

50 

 Frequency tolerance of input voltage, %

± 1

 Supply voltage of lighting circuits of alternating current of frequency 50 Hz, V

220 

 Supply voltage alarm system from the battery (through the switch), V

220 

 Tolerance of operating voltage,%

 +10;  -15

 Consumption on operational voltage circuits, W

30 

Write us

Your message has been send succesfully!
logo

Акционерное Общество "Уралэлектротяжмаш"

Yekaterinburg,
Frontovyh brigad, 22
+7 (343) 324-53-00
secretary@uetm.ru