/fs/cache/5c/26/f7/d4/afe79f28d603b17af82a0b6f.jpg

В-ТПЕД Rectifiers for 1000 and 2000 A Currents for Traction Substations

  • Types of manufactured rectifiers and transformers that go together with rectifiers are listed in the table:

Rectifier type

Transformer

V-TPED-1000-600М УХЛ4

TSZP-1000/10 GT UZ

V-TPED-2000-600М УХЛ4

TSZP-1600/10 GT UZ

V-TPED-1000-600Н УХЛ4

TSZPU-1000/10 GT UZ

V-TPED-2000-600М УХЛ4

TSZPU-2000/10 GT UZ

  • Climatic version of the rectifier - UHL for macroclimatic areas with a temperate and cold climate, placement category 4 according to GOST 15150-69 and GOST 15543.1-89.
  • The rectifier is designed to work when installed at a height of no more than 1000 m above sea level, the working value of the ambient air temperature is from + 1 to + 35 C and relative humidity of 60% at 20 C. Limit operating values of ambient air temperature from + 1 to + 40 C and relative humidity of air 80% at 25 C.
  •  The V-TPED rectifier has a microprocessor control, protection and alarm system (based on Siemens), which allows you to adapt this device to the automated control system of the traction substation complex.

Parameters

Parameters

Values

V-TPED-1000-600М

V-TPED-1000-600Н

V-TPED-2000-600М

V-TPED-2000-600Н

Rated output power, kW

600

1200

Frequency of mains voltage, Hz

50(60)

Frequency tolerance of input voltage, Hz

± 0,4

Rectification scheme

Three-phase bridge

Six-phase with balancing reactor

Three-phase bridge

Six-phase with balancing reactor

Nominal output voltage, V

600

Rated output current, A

1000

2000

Diode type

Д153-2500-20

Д143-1250-20

Д163-3200-20

Д153-2500-20

The number of consecutive diodes in the shoulder

2

Number of diodes

12

Efficiency,% (calculated value), not less

97,4

Power factor (at loads from 60% to 125% nominal), not less

0,93

Cooling

Natural air

Rated auxiliary power supply voltage from an AC network of a traction substation, V

220

Allowable voltage deviation of auxiliary needs of an alternating current traction substation, %

+10; -15

Power consumption by own needs, kW, not more

0,25

Control, protection and alarm system

microprocessor

Nominal input voltage of the converter transformer, kV

6,3; 10,0 

6,0; 6,3; 10,0; 10,5

6,3; 10,0 

6,0; 6,3; 10,0; 10,5

Nominal output line voltage of a valve winding of a converter transformer, V

475

565

475

565

Rectifier dimensions, mm (length x width x height)

800 х 800х 2200

800 х 1000х 2200

800 х 800х 2200

Notes:

1 The efficiency value is indicated together with the converter transformer.

2 The tolerance of the input voltage is ± 10%, while the output voltage is not normalized.

Write us

Your message has been send succesfully!
logo

Акционерное Общество "Уралэлектротяжмаш"

Yekaterinburg,
Frontovyh brigad, 22
+7 (343) 324-53-00
secretary@uetm.ru