SF6 Gas Column Circuit Breakers ВГТ-УЭТМ®-500

Circuit Breakers are applied in commutation of power networks in normal and emergency modes as well as operation in АПВ cycles in AC three-phase networks 50 Hz and rated voltage 500 kV

 There are two climatic versions: У and ХЛ*, location categories 1 GOST 15150-69 and GOST 15543.1 for operation out/indoor switchgears in temperate and cold climatic conditions

 Lower limits of ambient air temperature: for У1 version: minus 45 оС with SF6 gas filling; for ХЛ1* version: minus 52 оС with filling with gas mixture

 The upper ambient temperature limit is +40 оС

 By request we can also supply Т1 version with the upper temperature limit +50 оС

 Three-pole version: three poles are independent; they are controlled by one spring drive ППВ-УЭТМ®

 High factory readiness; simple and quick installation and commissioning

 Natural leakage level - below 0,5 % per year

 Circuit breaker’s insulation keeps the electrical strength at voltage 1,15 of the maximum phase voltage in case of gas overpressure lack

 Capacitive currents switched off without repeated breakthroughs; low overvoltage

 Low noise level at operation – according to high environmental requirements

 We can supply an accounting device for switching service life or a synchronous control device including switch life time accounting (for single-pole version).

 We can also supply a distribution cabinet.

Parameters

1.

№ 

Parameters

ВГТ-УЭТМ®-500

1

Rated voltage, kV

500

2

Max operating voltage, kV

525

3

Rated current, A

4000

4

Rated breaking current, kA

40

5

Rated aperiodic component, %, maximum

47

6

Rated through short-circuit current, kA:

Peak (electrical endurance);

100

Root-mean-square current value during its flow (thermal stability current);

40 

Thermal stability current time, s.

3

7

Rated parameters of making current, kA:

Peak;

100

Initial value of periodic component.

40

8

Commutation of capacitive current (class С1):

Rated commutation current of unloaded air line, А;

500

Rated commutation current of cable line, А;

500

Rated commutation current of single capacitor bank, А.

400

9

Rated breaking current of shunt reactor, А

315±63

10

Minimum breaking current of shunt reactor, А

100±20

11

Own breaking time, s

0,018…0,025

12

Total breaking time, s

0,050

13

Own making time, s, max

0,070

14

Diversity of poles operation, s, max

At making

0,005

At breaking

0,0033

15

Annual gas leakage rate, % of gas mass, max

0,5

16

Test lightning impulse, kV:
To earth / between open contacts

1550   / 1850

17

Test commutation impulse voltage, kV:
To earth / between open contacts

1230   / 1660

18

Testing one-minute voltage of commercial frequency, kV:
To earth / between open contacts

760 /1030

19

Rated DC voltage of the drive control magnets, V

110 или 220

20

Number of control magnets:

making

1

breaking

2

21

  Breaking current of commutation contacts for auxiliary circuits (drive)

14НО + 14НЗ + 2 sliding

22

Spring wind up motor power for making springs, kW

2х1,175

23

Rated voltage of motor of making springs, V

=110, = 220 or ~230

24

Time of making springs winding up, s, max

15

25

Rated capacity of drive heaters, W:

Continuous anti-condensate heating;

50

Main heating automatically turns up at lower temperature

600

26

AC voltage of feeding heaters, V

230

27

Max. vertical dynamic force on the foundation of 1 of 4 supports of the pole at CB operation (w/o own weight), kN:

upward

55,4

downward

41,9

28

Max static load on  the foundation of 1 of 4 supports of the pole , kN

8,8

29

Circuit breaker’s weight w/o metal supports, kg, maximum       

9700

2. Cycles and Operations of Circuit Breakers:

 Breaking (О);

Making (В);

Making-breaking (ВО) including – without intended delay between operations (В) and (О);

Breaking - making (ОВ) at any contact-free pause;

Breaking – making - breaking (ОВО) with intervals between operations according to items 3 & 4;

Commutation cycles:

О - 0,3с  – ВО - 180с - ВО;

О - 180с – ВО - 180с – ВО.

 3. Permissible breaking operations number for each pole without review and maintenance of arc chutes (commutation stability lifespan) at short-circuit currents and load currents:

 At the current 100% of the rated breaking current: 15 operations

At the current 60 % of the rated breaking current: 26 operations

At the operating currents equal to 3150A: 5000 operations «Making-random pause-breaking».

At the operating currents equal to 4000A: 1700 operations «Making-random pause-breaking»

 Permissible number of making operations for short-circuit currents should be not more than 50% of the permissible breaking operations; permissible making operations at load currents is equal to permissible breaking operations.

 4. Reliability of Circuit Breakers:

 Mechanical strength before overhaul maintenance: 10000 operations «Making –random pause - breaking» with no current in the main circuit;

Lifespan before the first maintenance at least 25 years, provided that mechanical strength or communication stability life was not spent. Maintenance necessity is judged by diagnostics of the circuit breaker technical condition;

Circuit breaker lifespan before retirement at least 40 years.

 5.  Absolute pressure of gas brought to temperature plus 20°С, MPa

Versions Т1 and У1

Version ХЛ1*

 

Filling pressure (nominal)

0,5

0,7

Warning alarm pressure

0,44

0,62

Locking pressure

0,42

0,6

6. Weight of gas required for filling circuit breaker, kg

Versions Т1 and У1

Version ХЛ1*

 

SF6 gas

SF6 gas

Tetra fluorine methane

 

56,2

39,6

22,3

21,0

 

 

 