SF6 Gas Column Circuit Breakers ВГТ-УЭТМ®-1А1-220

The circuit breaker is designed for switching electrical circuits under normal and emergency modes, as well as operating in automatic recloser cycles in three-phase AC 50 Hz networks with a rated voltage of 220 kV.

  • The circuit breakers are made in climatic versions of U and HL *, placement category 1 GOST 15150-69 and GOST 15543.1. They are designed for operation in open and closed switchgear in temperate and cold climates.
  • The lower operating value of the ambient air switch temperature is: for version U1 - minus 45 ° С when filling the switch with gas, for version HL1 * - minus 55 ° С when filling the circuit breaker with gas mixture.
  • The upper working value of the temperature of the surrounding air switch is +40 ° C.
  • By request delivery in a climatic modification T1 is possible - the top working value of air temperature is +50 ° C.
  • Triple pole design: three poles (speakers with a one-shot arcing device) are placed on a common frame and are controlled by a single high-power spring drive.
  • High factory readiness, simple and quick installation and commissioning.
  • Natural leakage rate - no more than 0.5% per year.
  • Ability to disconnect the load current 3150 A with loss of gas overpressure.
  • Maintaining the electrical strength of the insulation of the switch when the voltage is equal to 1.15 of the highest phase voltage in the event of loss of excess gas pressure in the circuit breaker.
  • Disconnection of capacitive currents without repeated breakdowns, low overvoltage.
  • Low noise when triggered - meets high environmental requirements. 
  • Possibility of supplying a switching resource metering device or a synchronous switch control device with a switching resource metering function (for single-pole performance).
  • Possibility to supply distribution cabinet (for single pole version).

Parameters

 

Parameters

ВГТ-УЭТМ®-1А1-220

1

Rated voltage, kV

220

2

Max operating voltage, kV

252

3

Rated current, A

3150 

по заказу возможно 4000

4

Rated breaking current, kA

40

5

Rated aperiodic component, %, maximum

47

6

Rated through short-circuit current, kA:

Peak (electrical endurance);

100

Root-mean-square current value during its flow (thermal stability current);

40

Thermal stability current time, s.

3

7

Rated parameters of making current, kA:

Peak;

100

Initial value of periodic component.

40

8

Commutation of capacitive current (class С1):

Rated commutation current of unloaded air line, А;

125

Rated commutation current of cable line, А;

250

Rated commutation current of single capacitor bank, А.

400

9

Rated breaking current of shunt reactor, А

315±63

10

Minimum breaking current of shunt reactor, А

100±20

11

Own breaking time, s

0,018…0,025

12

Total breaking time, s

0,050

13

Own making time, s, max

0,070

14

Diversity of poles operation, s, max

At making

0,005

At breaking

0,0033

15

Annual gas leakage rate, % of gas mass, max

0,5

16

Test lightning impulse, kV:
To earth / between open contacts

900 / 900 / 1050

17

Testing one-minute voltage of commercial frequency, kV:
To earth / between open contacts

440 / 440 / 440

18

Rated DC voltage of the drive control magnets, V

=110 или = 220

19

Number of control magnets:

making

1

breaking

2

20

Operating voltage range of control magnets, % of the nominal value:

Making magnet

80-110

Breaking magnet

70-110

21

Rated value of the set DC consumed by magnets, А, max:

at 110V

5

at 220V

2,5

22

Number of contacts for auxiliary circuits (for the drive)

14НО + 14НЗ + 2 проскальзывающих

23

Breaking current of commutation contacts for auxiliary circuits at 110/220 V, A:

AC

25

DC

4/2

24

Spring wind up motor power for making springs, kW

2х1,175

25

Rated voltage of feeding single-phase AC/DC motor of making springs, V

=110, = 220 или ~230

26

Time of making springs winding up, s, max

15

27

Rated capacity of drive heaters, W:

Continuous anti-condensate heating;

50

Main heating automatically shuts down at lower temperature

600

28

AC voltage of feeding heaters, V

230

29

Max vertical dynamic force on foundation of one of four support plates of the pole at operation (w/o own weight), кН: 

Up

36,6

Down

27,8

30

Max static load on foundation of one of four support plates of the pole, kN

5,2

31

Static resultant force from cables and wind load in three perpendicular directions (А/В/С GOST R 52565), Н

2550 / 2300 / 1250

32

Weight of circuit breaker without metal support, kg, maximum:

 

Three-pole version

3500

 

Single-pole version

4650

 

2. Cycles and Operations of Circuit Breakers:

 

Breaking (О);

Making (В);

Making-breaking (ВО) including – without intended delay between operations (В) and (О);

Breaking - making (ОВ) at any contact-free pause;

Breaking – making - breaking (ОВО) with intervals between operations according to items 3 & 4;

Commutation cycles:

О - 0,3с  – ВО - 180с - ВО;

О - 0,3с  – ВО - 20с - ВО;

О - 180с – ВО - 180с – ВО.

 

3. Permissible breaking operations number for each pole without review and maintenance of arc chutes (commutation stability lifespan) at short-circuit currents and load currents:

 

At the current 100% of the rated breaking current: 17 operations

At the current 60 % of the rated breaking current: 45 operations

At the operating currents equal to the rated current: 5000 operations «Making-random pause-breaking».

 

Permissible number of making operations for short-circuit currents should be not more than 50% of the permissible breaking operations; permissible making operations at load currents is equal to permissible breaking operations.

 

4. Reliability of Circuit Breakers:

 

Mechanical strength before overhaul maintenance: 10000 operations «Making –random pause - breaking» with no current in the main circuit;

Lifespan before the first maintenance at least 25 years, provided that mechanical strength or communication stability life was not spent. Maintenance necessity is judged by diagnostics of the circuit breaker technical condition;

Circuit breaker lifespan before retirement at least 40 years.

 

5.  Absolute pressure of gas brought to temperature plus 20°С, MPa

 

Versions Т1 and У1

Versions ХЛ1*

 

Filling pressure (nominal)

0,5

0,7

Warning alarm pressure

0,44

0,62

Lock pressure

0,42

0,6

 

6. Gas weight required for filling a circuit breaker, kg

 

 

Versions Т1 and У1

Для исполнения ХЛ1*

 

SF6 gas

Элегаз

Тетрафторметан

ВГТ-УЭТМ®-1А1-220

20,5

14,0

8,2