Tank Circuit Breakers ВГБ-УЭТМ®-35

Gas-insulated tank circuit breakers for outdoor installation of the ВГБ-УЭТМ®-35 series are designed for switching electrical circuits under normal and emergency conditions, as well as for operating in standard cycles with automatic reclosing in three-phase AC networks of 50 and 60 Hz rated voltage of 35 kV.

  • Circuit breakers can operate in a wide range of climatic conditions: from the Far North (lower working value of the ambient temperature - minus 60 °C) to areas with a tropical climate (upper working temperature value + 55 °C)
  • Complete factory readiness for simple and quick installation, the CB is supplied fully regulated, filled with SF6 gas to the operating pressure.
  • Lack of dynamic loads on the foundation when working
  • No overvoltage even when disconnecting small inductive currents and disconnecting without repeated breakdown of capacitive currents up to 600 A
  • Reduced natural gas leakage rate
  • The big mechanical and switching resources providing work during normal operation conditions during all service life of the circuit breaker
  • High reliability: even if the excess pressure of the SF6 gas drops to zero, the circuit breaker withstands long-term exposure to 52 kV and cuts off load currents up to 600 A
  • 12 built-in current transformers TVG-UETM®-35, which in most cases allow to refuse the use of external current transformers of outdoor installation. More information about the used embedded current transformers can be found on the page TVG-UETM®

  • Explosion and fire safety

Parameters

Main Technical Characteristics:

Parameters

ВГБ-УЭТМ®-35

1

Rated voltage, kV

35

2

The largest operating voltage, kV

40,5

3

Rated current, А

630 or 1000

4

Rated breaking current, kА

12,5

5

The nominal relative content of the aperiodic component , %

32

6

Through current short circuit, kA:

highest peak

35

three-second current thermal resistance

12,5

7

Switchable capacitive current of a single capacitor battery, A, not more

600

8

Own breaking time, s

0,04 ± 0,005

9

Total  breaking time, s

0,06

10

Minimum dead time at ARC, s

0,3

11

Own making time, s, not more

0,1+0,03

12

The filling pressure of the gas, given to a temperature of 20 ° C, MPaabs. (kgf / cm2)

0,5 (5,0)

13

Pressure pre-alarm for leakage of gas, reduced to a temperature of 20 ° C, MPaabs. (kgf / cm2)

0,43 (4,3)

14

Alarm pressure (blocking) _ prohibition of operation or forced shutdown of the CB with the prohibition of switching on, reduced to a temperature of 20 ° C, MPaabs. (kgf / cm2) ( Development of a blocking scheme variant is carried out by the design organization in agreement with the operating organization.)

0,4 (4,0)

9

Annual leakage, %, max.

0,5

10

Test voltage of industrial frequency, effective value, kV:

one minute internal and external insulation

95

external insulation with a smooth rise:

 

Dry discharge

105

Under rain

85

11

Test voltage of lightning impulses, kV:

full impulse

190

cut impulse

230

12

Creepage distance of bushings with porcelain insulators (pollution category II * according to GOST 9920), cm

1051

13

Creepage distance of bushings with polymer insulators (pollution category III according to GOST 9920), cm

1261

14

Rated voltage of control electromagnets, V:

when powered by direct current

110; 220

when powered by alternative current

230

15

Operating voltage range of control electromagnets,% of nominal value:

including when powered by direct or rectified current

85 – 110

disconnecting when powered by direct current

70 – 110

disconnecting when powered by rectified current

65 – 120

16

Current consumption (maximum value in the process of switching on electromagnets), A, not more than:

making:

15

at Un = 220 V

38

at Un = 110 V

76

§ breaking: 5

 

at Un = 220 V

2,5

at Un = 110 V

5

17

Current tripping current (YAA) for circuits with de-shunting, A

5 ± 0.5 2

18

Rated voltage of trip units with independent power supply (YAV), V:

  when powered by direct current

230

  when powered by alternative current

2203

19

Operating voltage range of the YAV trip unit,% of the nominal value when supplied with direct or alternating current

65…120

20

Rated current of auxiliary circuits, A

10

21

Breaking current of the switching contacts for external auxiliary circuits, A, at voltage:

AC 127/230 V

10/10

DC 110/220 V

2/1

22

Number of free auxiliary contact circuits : 4

making

3

breaking

3

23

Power of heating devices, W, not more than: 

circuit breaker with porcelain external insulation performance UHL1

800

circuit breaker with polymeric external insulation performance UHL1

1600

anti-condensation heating of CB

32

Version drive:

 

Т1

50

UHL1

850

24

Power of anti-condensation heating drive, W

50

25

Voltage of heating devices, V

230

26

Rated operating current of the pressure detector, A:

short-term by making

1.0

short-term by breaking

1.0

steady value

0.6

switchable power W/VA

30/50

27

Voltage of switched circuits of pressure indicator, V, not more

220

28

Circuit breaker weight, kg

650

29

Weight of gas, kg

4

1  By special order it is possible to complete the CBs with entries with an increased creepage distance. .2  By separate order 3-amp current release can be supplied. 3  By a separate order, they can be supplied with independent release of direct current at a voltage of 110 V.4. By way of a separate order, additional CSAs are installed (6 N.W. + 6 N.O.).5  By request, a second shut-off electromagnet is installed, except for the PEM-UETM®-3 version.

Note:1. For circuit breakers with dependent drive power, the operating voltage range of the alternating current at the rectifier terminals is 200-242 V. The single-phase transformer power to supply the rectifier is at least 25 kV • A.  This ensures the inclusion of a latching on short circuit currents up to 12.5 kA. No inductive energy storage required.2. If it is necessary to increase the number of signal circuits, it is allowed to use both (closing and opening) contacts of the BKM node provided that the circuits have a common point (a jumper is installed between the closing and opening contacts of the BKM) and do not carry an inductive load.

The CB has the following reliability and durability:.

  • Resource on mechanical firmness before the first repair - 10,000 cycles “on-random pause-off” (В-tn-О without current in the main circuit).

Allowed for each pole of the CB without inspection and repair of arc-suppressing devices, contacts and replacement of SF6 gas, the number of shutdown operations (resource for switching resistance) is at least one of the values:

  • With currents Iо,ном– 33 breakings;
  • With currents 0,6 Iо,ном– 70 breakings;
  • At rated load current - 2000 operations (including operations of switching off capacitive currents up to 600 A of single capacitor batteries).

The permissible additional number of switching operations is 50% of the specified number of switching operations (at rated load current - 100%).