Parameters
|
ВГБ-УЭТМ®-35
|
1
|
Rated voltage, kV
|
35
|
2
|
The largest operating voltage, kV
|
40,5
|
3
|
Rated current, А
|
630 or 1000
|
4
|
Rated breaking current, kА
|
12,5
|
5
|
The nominal relative content of the aperiodic component , %
|
32
|
6
|
Through current short circuit, kA:
|
highest peak
|
35
|
three-second current thermal resistance
|
12,5
|
7
|
Switchable capacitive current of a single capacitor battery, A, not more
|
600
|
8
|
Own breaking time, s
|
0,04 ± 0,005
|
9
|
Total breaking time, s
|
0,06
|
10
|
Minimum dead time at ARC, s
|
0,3
|
11
|
Own making time, s, not more
|
0,1+0,03
|
12
|
The filling pressure of the gas, given to a temperature of 20 ° C, MPaabs. (kgf / cm2)
|
0,5 (5,0)
|
13
|
Pressure pre-alarm for leakage of gas, reduced to a temperature of 20 ° C, MPaabs. (kgf / cm2)
|
0,43 (4,3)
|
14
|
Alarm pressure (blocking) _ prohibition of operation or forced shutdown of the CB with the prohibition of switching on, reduced to a temperature of 20 ° C, MPaabs. (kgf / cm2) ( Development of a blocking scheme variant is carried out by the design organization in agreement with the operating organization.)
|
0,4 (4,0)
|
9
|
Annual leakage, %, max.
|
0,5
|
10
|
Test voltage of industrial frequency, effective value, kV:
|
one minute internal and external insulation
|
95
|
external insulation with a smooth rise:
|
|
Dry discharge
|
105
|
Under rain
|
85
|
11
|
Test voltage of lightning impulses, kV:
|
full impulse
|
190
|
cut impulse
|
230
|
12
|
Creepage distance of bushings with porcelain insulators (pollution category II * according to GOST 9920), cm
|
1051
|
13
|
Creepage distance of bushings with polymer insulators (pollution category III according to GOST 9920), cm
|
1261
|
14
|
Rated voltage of control electromagnets, V:
|
when powered by direct current
|
110; 220
|
when powered by alternative current
|
230
|
15
|
Operating voltage range of control electromagnets,% of nominal value:
|
including when powered by direct or rectified current
|
85 – 110
|
disconnecting when powered by direct current
|
70 – 110
|
disconnecting when powered by rectified current
|
65 – 120
|
16
|
Current consumption (maximum value in the process of switching on electromagnets), A, not more than:
|
making:
|
15
|
at Un = 220 V
|
38
|
at Un = 110 V
|
76
|
§ breaking: 5
|
|
at Un = 220 V
|
2,5
|
at Un = 110 V
|
5
|
17
|
Current tripping current (YAA) for circuits with de-shunting, A
|
5 ± 0.5 2
|
18
|
Rated voltage of trip units with independent power supply (YAV), V:
|
when powered by direct current
|
230
|
when powered by alternative current
|
2203
|
19
|
Operating voltage range of the YAV trip unit,% of the nominal value when supplied with direct or alternating current
|
65…120
|
20
|
Rated current of auxiliary circuits, A
|
10
|
21
|
Breaking current of the switching contacts for external auxiliary circuits, A, at voltage:
|
AC 127/230 V
|
10/10
|
DC 110/220 V
|
2/1
|
22
|
Number of free auxiliary contact circuits : 4
|
making
|
3
|
breaking
|
3
|
23
|
Power of heating devices, W, not more than:
|
circuit breaker with porcelain external insulation performance UHL1
|
800
|
circuit breaker with polymeric external insulation performance UHL1
|
1600
|
anti-condensation heating of CB
|
32
|
Version drive:
|
|
Т1
|
50
|
UHL1
|
850
|
24
|
Power of anti-condensation heating drive, W
|
50
|
25
|
Voltage of heating devices, V
|
230
|
26
|
Rated operating current of the pressure detector, A:
|
short-term by making
|
1.0
|
short-term by breaking
|
1.0
|
steady value
|
0.6
|
switchable power W/VA
|
30/50
|
27
|
Voltage of switched circuits of pressure indicator, V, not more
|
220
|
28
|
Circuit breaker weight, kg
|
650
|
29
|
Weight of gas, kg
|
4
|
1 By special order it is possible to complete the CBs with entries with an increased creepage distance. .2 By separate order 3-amp current release can be supplied. 3 By a separate order, they can be supplied with independent release of direct current at a voltage of 110 V.4. By way of a separate order, additional CSAs are installed (6 N.W. + 6 N.O.).5 By request, a second shut-off electromagnet is installed, except for the PEM-UETM®-3 version.
|
Note:1. For circuit breakers with dependent drive power, the operating voltage range of the alternating current at the rectifier terminals is 200-242 V. The single-phase transformer power to supply the rectifier is at least 25 kV • A. This ensures the inclusion of a latching on short circuit currents up to 12.5 kA. No inductive energy storage required.2. If it is necessary to increase the number of signal circuits, it is allowed to use both (closing and opening) contacts of the BKM node provided that the circuits have a common point (a jumper is installed between the closing and opening contacts of the BKM) and do not carry an inductive load.
|