Tank Circuit Breaker ВЭБ-УЭТМ®-220

Circuit breakers are designed for switching electrical circuits under normal and emergency modes, as well as working in reclosing cycles in three-phase AC 50 Hz networks with a rated voltage of 220 kV.

  • Circuit breakers can be manufactured in three-pole, two-pole or single-pole design:
  • Triple pole and double pole design: poles are placed on one frame and controlled by one high-power spring drive;
  • One-pole design: each pole is located on its own frame and has its own drive.
  • Circuit breaker is manufactured in a climatic version of UHL placement category 1 GOST 15150-69, GOST 15543.1 and is intended for operation in open and closed switchgear in areas with temperate and cold climates. 
  • The upper operating temperature value of the ambient air switch is +40 °С
  • The lower operating temperature of the ambient air switch is minus 60 °С
  • On request, it is possible to supply circuit breakers in climatic version T1 - the upper working value of the ambient air temperature +55 °С
  • The circuit breaker is equipped with electrical pole-heating devices, ensuring reliable operation of the switch in conditions of extremely low temperatures and wind load. With the help of temperature sensors installed in the electric heating devices, an alarm is provided regarding the correct operation of the heaters.
  • Presence of built-in current transformers of type ТВГ-УЭТМ®-220 with high accuracy classes and long calibration interval - 20 years. Up to six current transformers for commercial metering, measurement and protection can be installed at the switch poles (up to eight current transformers per pole can be installed on special order).  More information about the used embedded current transformers can be found on the page TVG-UETM®
  • Complete set spring drive ППВ-УЭТМ®
  • Circuit breakers are equipped with high-strength porcelain or polymer insulators
  • Each pole is equipped with electrical contact density indicators for continuous monitoring of the pressure of the gas
  • Natural gas leakage rate - no more than 0.5% per year
  • Possibility of shutting down load currents when the excess pressure of the SF6 gas in the switch decreases to zero
  • Maintaining the electrical strength of the insulation of the switch when the voltage is equal to 1.15 of the highest phase voltage in the case of reducing the excess pressure of the gas to zero
  • Disconnection of capacitive currents without repeated breakdowns, low overvoltage
  • High factory readiness, quick installation and commissioning under the guidance of the plant's supervisors
  • High mechanical and switching resource, 5,000 nominal current breaking operations, 20 short-circuit current outages equal to 50 kA
  • Minimum maintenance
  • High fire and explosion safety

Low noise when triggered - meets high environmental requirements

Parameters

Наименование параметра

ВЭБ-УЭТМ®-220

1

Rated voltage, kV

220

2

Largest operating voltage, kV

252

3

Rated current, A

2500; 31501)

4

Rated breaking current, kA

50

5

Parameters of the through short circuit current, kA:

Highest current

125

initial effective value of the periodic component

50

Thermal current

50

Time course of thermal resistance, s

3

Номинальное относительное содержание апериодической составляющей, %, не более

47

6

Making current parameters, kA:

Highest current

125

initial effective value of the periodic component

50

7

Current unloaded lines, disconnecting without repeated breakdowns, A, not more

125

8

The current of a single capacitor battery, disconnected without repeated breakdowns, A

400

9

Shunt reactor current, А 

Minimum current

100

Normalized breaking current

315

10

Minimum dead time at ARC, s

0,3

11

Test one-minute voltage frequency 50 Hz, kV

440

12

Test voltage of a lightning impulse, kV
Relative to earth / between poles / between open contacts

900/900/1050

13

Creepage distance of external insulation, cm, not less: 

For degrees of air pollution  II*/III/IV

570/630/790

14

Drive type

Spring

15

Nominal supply voltage of the electric motor of the plant including springs, V

+220/~230 1 phase or =110

16

Power of electric motors of the springs, kW

2х1,0

17

Charging time of springs, s, not more

15

18

AC supply voltage of heating devices, V

230

19

Drive heating power, W:

Non-switchable (anti-condensate)

50

Main

600

20

Absolute pressure of the gas, MPa, at  20 °С: 

Filling pressure

0,7

Alarm pressure

0,62

Interlock pressure - prohibition on operation

0,60

21

Own breaking time, s

0,02+0,005/-0,002

22

Total breaking time, s

0,05

23

Own making time, s, not more

0,07

24

Weight of gas, kg :

3-pole design:

Porcelain Insulated

97

Polymer Insulated

111

2-pole design:

Porcelain Insulated

64

Polymer Insulated

74

1-pole design: 

Porcelain Insulated

33

Polymer Insulated

37

25

Mass of circuit breaker with the drive and KTT, kg: 

3-pole design:

 

Porcelain Insulated

5900

Polymer Insulated

4700

2-pole design:

Porcelain Insulated

3700

Polymer Insulated

2800

1-pole design:

Porcelain Insulated

2350

Polymer Insulated

1900

26

Total power of pole heaters, W:

3-pole design

12480

2-pole design

8320

1-pole design (1 pole)

4160

27

Operating voltage range of electromagnets,% of nominal value:

Making magnet

80-110

Breaking magnet

70-110

28

The nominal value of the steady-state value of the direct current consumed by the control electromagnets, A, not more than: 

at 110V

2

at 220V

1

29

Number of switching contacts for external auxiliary circuits

14 Н.О.+ 14 Н.З.+2

Slipping

30

Breaking current for switching contacts for external auxiliary circuits at voltage 110/220V, A: 

AC

25

DC

4/2

1) Only for circuit breakers with porcelain insulation