Tank Circuit Breakers ВЭБ-УЭТМ®-110-50

The circuit breakers are designed for switching electrical circuits under normal and emergency modes, as well as operating in automatic recloser cycles in three-phase AC 50 Hz networks with a rated voltage of 110 kV and a shutdown current of 50 kA.

  • Circuit breakers can be manufactured in three-pole, two-pole or single-pole design:
  • 3- and 2-pole design: poles are placed on one frame and controlled by a single spring drive;
  • 1-pole design: Each pole is located on its own frame and has its own drive.
  • Circuit breaker is manufactured in a climatic version of UHL placement category 1 GOST 15150-69, GOST 15543.1 and is intended for operation in open and closed switchgear in areas with temperate and cold climates. 
  • The upper operating temperature value of the ambient air switch is +40 °С
  • The lower operating temperature of the ambient air switch is minus 60 °С
  • On request, it is possible to supply circuit breakers in climatic version T1 - the upper working value of the ambient air temperature +55 °С
  • The circuit breaker is equipped with electrical pole-heating devices, ensuring reliable operation of the switch in conditions of extremely low temperatures and wind load. With the help of temperature sensors installed in the electric heating devices, an alarm is provided regarding the correct operation of the heaters.
  • Availability of built-in current transformers of type ТВГ-УЭТМ®-110 with high accuracy classes and long calibration interval - 20 years. Up to six current transformers for commercial metering, measurement and protection can be installed at the switch poles (up to eight current transformers per pole can be installed on special order).
  • Complete set spring drive type ППВ-УЭТМ®
  • The circuit breakers are equipped with high-strength porcelain or polymer insulators.
  • Each pole is equipped with electrical contact density indicators for continuous monitoring of the state of the gas.
  • Natural gas leakage rate - no more than 0.5% per year.
  • Possibility of shutting down load currents when the excess pressure of the SF6 gas in the CB decreases to zero.
  • Disconnection of capacitive currents without repeated breakdowns, low overvoltage.
  • High factory readiness, quick installation and commissioning under the guidance of the plant's supervisors.
  • High mechanical and switching resource, 5,000 nominal current cut-off operations, 20 short-circuit current outages equal to 50 kA.
  • Minimum maintenance.
  • High fire and explosion safety.

Low noise when triggered - meets high environmental requirements.

Parameters

Parameters

ВЭБ-УЭТМ®-110-50

Rated voltage, kV

110

The largest operating voltage, kV

126

Rated current, A

2500; 31501)

Rated breaking current, kА

50

Parameters of the through short circuit current, kA:

- highest peak

125

-  initial effective value of the periodic component

50

-  thermal current

50

-  time of thermal current stability, s

3

-  nominal relative aperiodic content  составляющей, %

47

Parameters of making current, kА

- highest peak

125

-  initial effective value of the periodic component

50

Current unloaded lines, disconnecting without repeated breakdowns, A, not more

125

The current of a single capacitor battery, disconnected without repeated breakdowns, A

400

Shunt reactor shutdown current, А:

Minimum current;

100

rated breaking current

315

10 

Minimum dead time at ARC, s

0,3

11 

Test one-minute voltage frequency 50 Hz, kV

230

12 

Test voltage of a lightning impulse, kV
relative to earth / between poles / between open contacts

550/550/550

13 

Creepage distance of external insulation, cm, not less

-  for degrees of air pollution  II* / III / IV

280/315/390

14 

Drive type

Spring

15 

Number of drives

1

16 

Nominal supply voltage of the electric motor of the making springs charging, V

~ 230-220 or -110

17 

Power of electric motors of the springs, kW

2х1,0

18 

Charging time of springs, s, not more

15

19 

AC supply voltage of heating devices, V

230

20 

Operating voltage range of control electromagnets,% of nominal value:

Making magnet

85-110

Breaking magnet

70-110

21 

The steady-state value of the direct current consumed by the control electromagnets, A, not more than:

at 110 V

2

at 220 V

1

22 

Number of switching contacts for external auxiliary circuits (per drive)

14Н.О.+14Н.З.

+2 slippping

23 

Breaking current for switching contacts for external auxiliary circuits at voltage  110/220 V:

AC

25

DC

4/2

24 

Rated power of heating devices, W:

а) drive 

non-switchable (anti-condensate)

50

- main

600

б) circuit breaker 

non-switchable (anti-condensate)

35

main 1 stage

6240

main 2 stage

6240

25 

Absolute pressure of the gas, MPa, at 20 °С:

Filling pressure

0,70

Alarm pressure

0,62

blocking pressure - prohibition of operation

0,6

26 

SF6 gas consumption per leakage per year,% by weight of SF6 gas, not more than

0,5

27 

Average weight of the circuit breaker with the drive, kg:

Porcelain Insulated

4750

Polymer Insulated

3900

28 

Mass of the gas in CB, kg

Porcelain Insulated

80

Polymer Insulated

72

29 

Climatic modification and category of placement in accordance with GOST 15150-69

УХЛ1

1) Only for CBs with porcelain insulation

Write us