Tank Circuit Breakers ВЭБ-УЭТМ®-110

Circuit breakers are designed for switching electrical circuits under normal and emergency modes, as well as working in reclosing cycles in three-phase AC networks of 50 Hz frequency with a rated voltage of 110 kV.

  • Circuit breakers can be manufactured in three-pole, two-pole or single-pole design:
  • Triple-pole and double-pole design: the poles are placed on the same frame and are controlled by a single spring drive;
  • Single-pole design: each pole is located on its own frame and has its own drive.
  • Circuit breakers are manufactured in climatic versions U *, UHL *, UHL placement categories 1 GOST 15150-69, GOST 15543.1 and are intended for operation in open and closed switchgear in areas with a temperate and cold climate
  • The upper operating temperature value of the ambient air switch is +40 °С
  • The lower operating temperature of the ambient air switch is:
  • For climatic version U1* – minus 40 °С;
  • For climatic version UHL1* – minus 55 °С;
  • For climatic version UHL1 – minus 60 °С;
  • On request it is possible to supply CBs in climatic version T1 - the upper working value of the ambient air temperature +55 °С
  • The CB in climatic modifications of UHL1 *; UHL1 is equipped with poles electrically heated devices, ensuring reliable operation of the CB in conditions of extremely low temperatures and wind load. With the help of temperature sensors installed in the electric heating devices, an alarm is provided regarding the correct operation of the heaters.
  • Availability of built-in current transformers of type ТВГ-УЭТМ®-110 with high accuracy classes and long calibration interval - 20 years. Up to six current transformers for commercial metering, measurement and protection can be installed at the switch poles (up to eight current transformers per pole can be installed on special order).  More information about the used embedded current transformers can be found on the page TVG-UETM®
  • Complete set spring drive ППрК-УЭТМ®
  • The CBs are equipped with high-strength porcelain or polymer insulators
  • Each pole is equipped with electrical contact density indicators to continuously monitor the pressure of the gas
  • Natural gas leakage rate - no more than 0.5% per year
  • Possibility of shutting down load currents when the overpressure of the SF6 gas in the circuit breakers decreases to zero.
  • Maintaining the electrical strength of the insulation of the CB when the voltage is equal to 1.15 of the highest phase voltage in the case of reducing the excess pressure of the gas to zero
  • High factory readiness, quick installation and commissioning under the guidance of the plant's supervisors
  • High mechanical and switching resource, 5,000 nominal current cut-off operations, 20 short-circuit current trips equal to 40 kA.
  • Minimal technical maintenance
  • High fire and explosion safety

Low noise when triggered - meets high environmental requirements

Parameters

Parameters

ВЭБ-УЭТМ®-110

1

Rated voltage, kV

110

2

The largest operating voltage, kV

126

3

Rated current, A

2500; 31501)

4

Rated breaking current, kА

40

5

Making current, kА: 

Highest current

102

initial effective value of the periodic component

40

6

Through current of short circuit, kA: 

Highest peak

102

initial effective value of the periodic component

40

thermal current

40

the time course of thermal resistance, s

3

7

Nominal relative content of aperiodic component,%, not more than

40

8

Current unloaded lines, disconnecting without repeated breakdowns, A, not more

31,5

9

The current of a single capacitor battery with a low-grounded neutral, disconnected without repeated beatings, A

0-300

10

Disconnectable inductive current shunt transformer, A

500

11

Disconnectable magnetizing current of unloaded transformers, A

8,5

12

Own breaking time, s

0,035-0,005

13

Total breaking time, s

0,055-0,005

14

Own making time, s, max.

0,062-0,018

15

SF6 gas consumption per leakage per year,% by weight of SF6 gas, not more than

0,5

16

Absolute pressure of the gas, MPa

Filling pressure (nominal)

0,5

Alarm pressure

0,44

Blocking pressure (prohibition of operating or switching off the CB with prohibition of switching on)

0,42

17

Current transformers2

Quantity for electric power metering and accounting devices and for relay protection devices per pole, pcs.

up to 8

Rated primary current, A

from 100 to 3150

Rated secondary current, A

5 or 1

Accuracy classes:

For measurement

0,2S; 0,2; 0,5S; 0,5; 1

For protection

5P; 10P; 5PR; 10PR; TPY; TPZ

Nominal secondary loads, VA : 

For measurement

up to 100

For protection

Up to 100

Safety factor for measuring transformers

from 2 to 30

Maximum frequency ratio of transformers for protection

 

from 2 to 250

18

The number of control electromagnets in the drive: 

making

1

breaking

2

19

Rated voltage DC electromagnets control drive, V3

110 or 220

20

Operating voltage range of electromagnets,% of nominal value: 

Making magnet

80-110

Breaking magnets

65-120

21

The nominal value of the steady-state value of the direct current consumed by the control electromagnets, A, not more than: 

at 110 V

5

at 220 V

2,5

22

Number of switching contacts for external auxiliary circuits

12 НО+ 12 НЗ+2
slipping

23

Breaking current for switching contacts for external auxiliary circuits at voltage  110/220В, А: 

AC

10/10

DC

2/1

24

Power of the electric motor of the plant including springs, kW : 

3-phase

1,1

Universal

0,75

25

Rated voltage of the electric motor of the factory of switching springs, V :

3-phase AC

230 or 400

DC or 1-phase AC

220 or 230

DC

110

Charging time of springs, s, not more

15

AC voltage of heating devices, V

230

26

Power of heating devices, V : 

Drives: 

Non-switchable (anti-condensate)

50

Basic (automatically turned on at low temperatures)

 

1st heating stage (activated at  0 °С)

800

2nd heating stage (activated at  – 20 °С)

800

CB: 

Non-switchable (anti-condensate)

30

Main for CB in tripolar design

2810 (УХЛ1*), 4730 (УХЛ1)

Main for CB in two-polar design

1890 (УХЛ1*), 3170 (УХЛ1)

Main for CB in one-polar design

970 (УХЛ1*), 1610 (УХЛ1)

27

Gas weight, kg

3-pole design 

Porcelain Insulated

27,3

Polymer Insulated

26,4

2-pole design 

Porcelain Insulated

18,2

Polymer Insulated

17,6

1-pole design 

Porcelain Insulated

9,1

Polymer Insulated

8,8

28

Mass of the CB with the drive and KTT, kg  

3-pole design  

Porcelain Insulated

2750

Polymer Insulated

2520

2-pole design  

Porcelain Insulated

2100

Polymer Insulated

1600

1-pole design  

Porcelain Insulated

1250

Polymer Insulated

1100

1) For porcelain insulated CBs only.

2) By the additional order current transformers with other parameters can be made.

3) It is allowed to supply electromagnets with control of rectified current, for example, from the blocks: BPT-1002, BPNS-2, and also BPZ-401 with blocks of capacitors BK-403.

2. Circuit breakers perform the following operations and cycles:

  • Breaking (B);
  • Making (M);
  • Making-breaking (MB) including without intentional time delay between operations (M) and (B);
  • Breaking - making (BM) during any contactless pause, starting from tбк of the related tбт;
  • Breaking – making - breaking (BMB) with the time intervals between operations according to the above points;
  • switching cycles:
  • B-0,3с-MB-180с- MB;
  • B-0,3с- MB -20с- MB;
  • B-180с- MB -180с- MB.

3. Permissible for each pole of the circuit breaker without inspection and repair of arc-suppressing devices, the number of shutdown operations (resource for switching resistance) is:

  • at currents in the range from 60 to 100% of the rated tripping current - 20 operations (thus, for a three-pole switch, the total switching resource is 60 operations in this current range);
  • at operating currents equal to the nominal current of 5000 operations “making-random pause-breaking”.

The permissible number of switching operations for short-circuit currents for each pole must additionally be no more than 50% of the permissible number of breaking operations.

The allowed number of making operations for load currents is equal to the allowed number of breaking operations.

4. Circuit breakers have the following reliability and durability:

  • resource for mechanical stability before overhaul - 10,000 cycles "making - random pause-breaking" (M – tn – B)
  • Service life - at least 40 years;

Warranty period - 5 years