/fs/cache/51/e4/34/3f/e3f829c49a4d9d346d089a93.jpg

ВАБ-UEТМ®-49/1

Automatic high-speed circuit breakers
WAB-UETM®-49/1-3200/30-L-UHL4, WAB-UETM®-49/1-5000/30-L-UHL4, (hereinafter Circuit Breakers), are used to protect the equipment of traction substations, points of parallel connection and sections of electrified railway transport from short-circuit currents and unacceptable overloads.

The circuit breakers are used in a single version.

Parameters

Parameters

Norms

WAB-UETM®-49/1-3200/30-L-UHL4

WAB-UETM®-49/1-5000/30-L-UHL4

  1. Main circuit current

DC

  1. Rated voltage of the main circuit, V

3300

  1. Maximum operating voltage, V

4100

  1. Rated current at a constant load in time, A

3200

5000

  1. Nominal DC voltage of control circuits, V

110 or 220

  1. Type of current sensor

РДШ-3000

РДШ-6000

  1. Current limits of the setpoint, A

800-4000

2000-4000

or

4000-7000

Breaking capacity, A

- in a non-inductive circuit
- with inductance of 5 - 15 mH

 

25000

35000

  1. Own opening time, s

0,008

  1. Total breaking time, s

-  in a non-inductive circuit

-  with inductance of  8 mH

-  with inductance of  15 mH

 

0,020

0,030

0,050

  1. The number of trips without stripping contacts and arc chamber

- 25000 А  in a non-inductive circuit

- 35000 А  inductive

5 – 15 mH

- 25000 А  inductive

5 – 15 mH

 

 

10

 

25

 

 

100

  1. Resource for mechanical wear resistance (number of inclusions and shutdowns in the absence of current in the main circuit), cycles

 

 

 

50000

  1. Weight of circuit breakers without spare parts and accessories, kg, not more than

 

130

 

164

  1. Mass of spare parts and hardware and equipment, kg, not more

 

22

 

38

  1. Breaker service life, years

20

Write us