ВАБ-UEТМ®-49/1
Automatic high-speed circuit breakers
WAB-UETM®-49/1-3200/30-L-UHL4, WAB-UETM®-49/1-5000/30-L-UHL4, (hereinafter Circuit Breakers), are used to protect the equipment of traction substations, points of parallel connection and sections of electrified railway transport from short-circuit currents and unacceptable overloads.
The circuit breakers are used in a single version.
Parameters
Parameters
|
Norms
|
WAB-UETM®-49/1-3200/30-L-UHL4
|
WAB-UETM®-49/1-5000/30-L-UHL4
|
- Main circuit current
|
DC
|
- Rated voltage of the main circuit, V
|
3300
|
- Maximum operating voltage, V
|
4100
|
- Rated current at a constant load in time, A
|
3200
|
5000
|
- Nominal DC voltage of control circuits, V
|
110 or 220
|
- Type of current sensor
|
РДШ-3000
|
РДШ-6000
|
- Current limits of the setpoint, A
|
800-4000
|
2000-4000
or
4000-7000
|
Breaking capacity, A
- in a non-inductive circuit - with inductance of 5 - 15 mH
|
25000
35000
|
- Own opening time, s
|
0,008
|
- Total breaking time, s
- in a non-inductive circuit
- with inductance of 8 mH
- with inductance of 15 mH
|
0,020
0,030
0,050
|
- The number of trips without stripping contacts and arc chamber
- 25000 А in a non-inductive circuit
- 35000 А inductive
5 – 15 mH
- 25000 А inductive
5 – 15 mH
|
10
25
100
|
- Resource for mechanical wear resistance (number of inclusions and shutdowns in the absence of current in the main circuit), cycles
|
50000
|
- Weight of circuit breakers without spare parts and accessories, kg, not more than
|
130
|
164
|
- Mass of spare parts and hardware and equipment, kg, not more
|
22
|
38
|
- Breaker service life, years
|
20
|
|
|
|
|