Current Transformers ТРГ-UEТМ®-35

The current transformers of the TRG series are designed to transmit measurement information signals to measuring devices and protection and control devices in 50 Hz or 60 Hz alternating current installations with a rated voltage of 35 kV.

  • Transformers are intended for operation in open and closed switchgears in the temperature range from + 40 ° С to minus 60 ° С (climatic version of UHL placement category 1), non-explosive environment, not containing aggressive gases and vapors in concentrations that destroy metals and insulation. 
  • High precision winding class for measurement - up to the commercial electricity metering class 0,2S

 Ability to manufacture a transformer with a special set of secondary windings (for example, with two windings for measurement)

  • Lack of internal solid insulation eliminates the occurrence of partial discharges, allows not to conduct periodic inspections and tests of insulation, and also minimizes the likelihood of internal breakdown of insulation
  • Reinforced mounting of the rack with the active part ensures the safety of the product even in harsh transportation conditions and under any dynamic loads during operation
  • By special order, it is possible to supply transformers with factory supporting metalwork covered with hot zinc

Parameters

General specifications

 

Parameters

TRG-UETM®-35

1

Rated voltage, kV

35

2

The largest operating voltage, kV

40,5

3

Voltage of industrial frequency withstand by transformer with pressure of insulating gas equal to atmospheric, kV

26

4

Nominal frequency, Hz

50 or 60

5

Rated primary current, in increments of 5A, A

from 5 to 2000

6

Rated secondary current, A

from 1 to 5

7

Number of secondary windings

from 1 to 4

8

Short-circuit current parameters:

Largest peak, kA

102

One-second current thermal resistance, kA

40

9

Maximum ambient temperature, °С:

For Т1

+50

For U1, UHL1*, HL1*, HL1

+40

10

Minimum ambient temperature according to GOST 15150-69, °С:

For  Т1

- 10

For  U1

- 45

For  UHL1

- 60

11

Insulating gas:

For  Т1

SF6 or N2

For  U1

SF6 or N2

For  UHL1

SF6 or N2

For HL1

-

12

Maximum allowable gas leakage,% per year

0,2

13

Maximum wind speed, m / s., with an ice wall thickness of up to 20 mm

40

14

Wire tension:

in the horizontal plane along the axis of the transformer, N

500

in the vertical plane down, N

500

15

The average weight of the transformer, kg:

with porcelain insulator

190

with polymer insulator

-

16

Average service life of the transformer, years, not less

40

The current transformer of the TRG series is a structure, in the upper part of which there is a metal case fixed on the supporting insulator. The insulator, in turn, is fixed on the base in which the terminal box of the secondary windings is located. The primary winding and its terminals are fixed in the metal case, the secondary windings are placed inside the case. The internal cavities of the housing and the insulator are filled with insulating gas.

The design of the primary winding allows to obtain different transformation ratios when changing the number of turns by a series-parallel connection of sections of the primary winding. It is possible to manufacture current transformers without switching with one transformation ratio.

The secondary windings are placed in electrostatic screens, in order to level the internal electric field.

The magnetic core of the secondary winding for measurement is made of nanocrystalline alloy, the magnetic core of the secondary winding for protection is made of cold-rolled anisotropic electrical steel.

The gas pressure is controlled using a density detector with temperature compensation. Density detector is equipped with two pairs of contacts, which allows receiving a signal at two gas density (pressure) values and remotely monitoring gas pressure.

If necessary, there is the possibility of sealing the findings of the secondary winding for electricity metering. Sealing is carried out in any convenient way. For this purpose, special places are provided in the design of the transformer. A protective device is located in the upper part of the current transformer, which connects the internal gas volume with the atmosphere when the internal pressure is significantly exceeded (for example, with excessive gas or internal arc overlapping), which makes the device explosion-proof.

Metrological parameters of secondary windings

Application

Accuracy class according to GOST 7746-2001 and IEC 60044-1-2003, 60044-6-92

Nominal secondary load, V ∙ A

Instrument safety factor

Nominal limit frequency

Commercial Accounting or Measurement

0,2S; 0,5S; 0,2; 0,5; 1; 3; 5

Up to 100

from 2 to 30

 

Protection

5Р; 10Р; 5PR; 10PR; TPY; TPZ

Up to  100

 

from 2 to 250