/fs/cache/51/a0/76/dc/e5e1fc079b25f17756f243d0.jpg

SF6 Gas Column Circuit Breakers ВГТ-УЭТМ®-35

The circuit breakers are designed for switching electrical circuits under normal and emergency modes, as well as operating in automatic reclose cycles in three-phase AC 50 Hz networks with a rated voltage of 35 kV.

  • The circuit breakers are made in climatic versions of U and HL *, placement category 1 GOST 15150-69 and GOST 15543.1. They are designed for operation in open and closed switchgear in temperate and cold climates.
  • The lower operating value of the temperature of the surrounding air switch is: for version U1 - minus 45 ° C when the switch is filled with gas, for version HL1 * - minus 55 ° C when the switch is filled with gas mixture.
  • The upper working value of the temperature of the surrounding air switch is +40 ° C
  • By request delivery in a climatic modification T1 is possible - the top working value of air temperature is +50 ° C
  • The switch is controlled by a spring drive, with an electric motor of the spring factory and various versions of the motor supply voltage
  • High factory readiness, simple and quick installation and commissioning
  • Natural leakage rate - no more than 0.5% per year
  • Ability to turn off load currents in case of loss of excess gas pressure in the switch 
  • Maintaining the electrical strength of the insulation of the switch when the voltage is equal to 1.15 of the highest phase voltage in the event of loss of excess gas pressure in the switch
  • Disconnection of capacitive currents without repeated breakdowns, low overvoltage
  • Low noise when triggered - meets high environmental requirements  
  • Possibility of supplying a switching resource metering device or a synchronous switch control device with a switching resource metering function (for single-pole performance).
  • Possibility to supply distribution cabinet (for single pole version).

Parameters

1. General technical characteristics:

Parameters

ВГТ-УЭТМ®-35

1

Rated voltage, kV

35

2

Max operating voltage, kV

40,5

3

Rated current, A

3150

4

Rated breaking current, kA

50

5

Rated aperiodic component, %, maximum

40

6

Rated through short-circuit current, kA:

Peak (electrical endurance);

125

Root-mean-square current value during its flow (thermal stability current);

50

Thermal stability current time, s.

3

7

Rated parameters of making current, kA:

Peak;

100

Initial value of periodic component.

40

8

Commutation of capacitive current (class С1):

Rated commutation current of unloaded air line, А;

-

Rated commutation current of cable line, А;

-

Rated commutation current of single capacitor bank, А.

-

9

Rated breaking current of shunt reactor, А

-

10

Minimum breaking current of shunt reactor, А

-

11

Own breaking time, s

0,035-0,005

12

Total breaking time, s

0,055-0,005

13

Own making time, s, max

0,062-0,018

14

Diversity of poles operation, s, max

At making

0,005

At breaking

0,0033

15

Annual gas leakage rate, % of gas mass, max

0,5

16

Test lightning impulse, kV:
To earth / between open contacts

190/190

17

Testing one-minute voltage of commercial frequency, kV:
To earth / between open contacts

95/95

18

Rated DC voltage of the drive control magnets, V

=110,

= 220 или ~230

19

Number of control magnets:

making

1

breaking (depends upon an order)

2 или 3

20

Operating voltage range of control magnets, % of the nominal value:

Making magnet

80-110

Breaking magnet

65-120

21

Rated value of the set DC consumed by magnets, А, max:

at 110V

5

at 220V

2,5

22

Number of contacts for auxiliary circuits (for the drive)

12НО + 12НЗ + 2 проскальзывающих

23

Breaking current of commutation contacts for auxiliary circuits at 110/220 V, A:

AC

10/10

DC

2/1

24

Spring wind up motor power for making springs, kW (one drive)

Three-phase

1,1

Universal

0,75

25

Rated voltage for feeding wind up motor, V:

 

Three-phase AC

230 или 400

Universal one-phase DC/AC

~230 или  =220

DC

110

26

Time of making springs winding up, s, max

15

27

Rated capacity of drive heaters, W:

Continuous anti-condensate heating;

50

Heating with automatic switch-off at low temperatures:

1 stage (on at 0°С)

800

2 stage (on at minus 20°С)

800

28

AC voltage for feeding the heaters, V

230

29

Maximum vertical dynamic force per one foundation support when circuit breaker operates (w/o own weight), кН

up

17,3

down

18,4

30

Max static load per one foundation support, kN

9,5

Прикрепленные файлы

Write us

Your message has been send succesfully!
logo

Акционерное Общество "Уралэлектротяжмаш"

Yekaterinburg,
Frontovyh brigad, 22
+7 (343) 324-53-00
secretary@uetm.ru